GE Logo
Home Products & Services Industries News/Events About Us Resources Contact Store
Home > Grid Automation > Automation & Control > Metering > EPM 6010
Product Lookup
Protection & Control Online Store (new window)
Protection & Control Support
Event Calendar
Protection & Control Press Room
Related Links
  EPM 2200
  EPM 6000
  EPM 6100
  EPM 7000
  EPM 7100
  EPM 9900
  Multilin Meter Enclosure
 
Resources
  Brochures
  Instruction Manuals
  Specifications
  Software
  Support
 
Subscribe
 
EPM 6010 Building Automation Power Meter
BACnet/IP Communications and Energy Measurement

The Multilin EPM 6010 is an industry leading revenue grade power meter with native BACnet/IP communications. This meter is designed to integrate seamlessly into existing and new building management systems using the popular BACnet protocol. The meter allows users to gather data on voltage, current, power and energy usage throughout a facility.

The EPM 6010T is a transducer configuration that comes without a display and has a DIN rail mount. GE Grid Solutions has discontinued sales of EPM 6010T based upon availability. As an alternative, please refer to the EPM6010 .

Key Benefits
  • • Rapid integration into BACnet management systems
  • • High accuracy, class revenue multifunction meter
  • • Compact, easy to install, fits ANSI and DIN cutouts
  • • User programmable for different system voltages and current measurements
  • • Standard Modbus TCP communications
  • • Easy to read, large 3 line .56" bright LED display for better visibility and longer life
Key Features

Communications

  • • BACnet/IP 100BaseT Ethernet protocol
  • • 40 predefined BACnet objects
  • • Embedded web server for remote configuration and viewing of BACnet/IP interface
  • • Standard Modbus TCP communications

Measuring and Metering

  • • 400+ samples per cycle and 24 bit A/D conversion
  • • Meets ANSI C12.20 (0.2%) and IEC 687 (0.2%) accuracy classes
  • • Total harmonic distortion (%THD)
  • • Graphical load percentage bar for visualization
  • • True RMS multifunction measurements

BACnet/IP Software Web interface Installation Specifications Transducer Enclosure
BACnet/IP COMMUNICATIONS

The Multilin EPM 6010 with BACnet/IP supports building energy management strategies, LEED certification and other Green Building initiatives. By allowing users to track energy use and power quality, the meters gives users the information they need to accurately identify cost -saving measures and respond to power quality problems when they arise.

 

Communications Ports
The Multilin EPM 6010 provides two independent communication ports with advanced features:

IrDA port – A unique optical IrDA port allows the unit to be setup and programmed using a remote laptop without needing a communication cable. Simply point at the meter with an IrDA-equipped PC computer to configure it.

Ethernet Port – This port provides connectivity via a 10/100BaseT RJ45 connection. Modbus TCP and BACnet protocols are supported


BACnet/IP Web Interface
The Multilin EPM 6010 comes standard with a web interface. Use the BACnet/IP interface to remotely set up the BACnet/ IP configuration and track energy use with any standard web browser. 


Simultaneous Communications Paths

Simultaneous Communications Paths
 
SOFTWARE OPTIONS
 

EnerVista Software
EnerVista Launchpad is a powerful software package that provides users a platform to access all of the setup and support tools needed for configuring and maintaining GE Multilin Products. Launchpad allows configuration of devices in real-time by communicating using RS232, RS485, Ethernet or modem connections. Using Launchpad as the single interface to the setup and analysis software makes it simple to enter setpoints, read metered values, monitor status and evaluate power quality.


Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use, full-featured monitoring and data recording software package for small systems. Viewpoint Monitoring provides a complete HMI package that instantly puts critical real-time device data on your PC through pre-configured graphical screens with the following functionality.

Plug-&-Play Device Monitoring

System Single-Line Monitoring & Control

Annunciator Alarm Screens

Trending Reports

Automatic Event Retrieval

Automatic Waveform Retrieval


EnerVista Integrator
EnerVista Integrator is a toolkit that allows seamless integration of GE Multilin devices into new or existing automation systems by sending GE device data to HMI, DCS, and SCADA systems. Included in EnerVista Integrator is:

OPC/DDE Server

GE Multilin Drivers

Automatic Event Retrieval

Automatic Waveform Retrieval



EnerVista Viewpoint Monitoring Data Recording and Real-Time Status


EnerVista Viewpoint Monitoring Data Recording and Real-Time Status
 
BACnet Web Interface

The Multilin EPM 6010 comes standard with a web interface. Use the BACnet/IP interface to remotely set up the BACnet/ IP configuration and track energy use with any standard web browser.

  BACnet Web Interface

 

 
MEASUREMENTS
 

Designed to be the perfect device for environmental initiatives, LEED certified projects and smart energy projects, the EPM 6010 provides superior metrology, and revenue testable 0.2% energy accuracy. The meter is in compliance with ANSI and IEC accuracy standards, has advanced DSP technology, samples at high rates, and has 24 bit A/D conversion to measure and analyze power accurately and reliably.


Measured Values
EPM 6010 measures the following values:


EPM6010 Measured Values

 
 
INSTALLATION
 

Universal Voltage and Current
This meter allows voltage input measurements up to 416 Volts Line to Neutral and 721 volts Line to Line. This helps ensure proper meter safety when wiring directly to high voltage systems. The unit will perform to specification on 69 Volt, 120 Volt, 230 Volt, 277 Volt and 347 Volt power systems.


Unique Current Input Connections

EPM 6010 meter uses two current input wiring methods.

Method One - CT pass through. Directly pass the CT through the meter without any physical termination on the meter.
This insures that the meter cannot be a point of failure on the CT circuit. This is preferable to utility users when sharing relay class CTs.
No Burden is added to the secondary CT circuit.

Method Two - Current "Gills." The meter additionally provides ultra-rugged termination pass through bars allowing the CT leads to be terminated on the meter. This also eliminates any possible point of failure at the meter. This method is also a preferred technique for ensuring relay class CT integrity does not get compromised. No terminal blocks are required and this stud based design ensures that CTs will not open under a fault condition.



 
EPM Installation

Through a standard Ethernet port, the EPM 6010 can easily integrate into systems using BACnet/IP or Modbus TCP.

Solid Construction with Mounting Versatility
The EPM 6010 has a rugged design for harsh environment. This is especially important in power generation, utility substation, and critical user applications. The structural and electrical design of this meter was developed based on the recommendations and approvals of many of our utility customers.

EPM 6010 can easily be mounted in a panel for generator monitoring, substation automation and more. The unique dual design combines ANSI and DIN mounting structure and allows easy installation for both new metering applications and retrofit of existing analog meters.

The unit mounts directly in an ANSI C39.1 (4" Round form) or an IEC 92 mm DIN square form.

Meter Interface

Meter Interface
 
SPECIFICATIONS

EPM6010 Specifications

EPM 6010T TRANSDUCER OPTION
EPM6010 Features

GE Grid Solutions has discontinued sales of EPM 6010T. As an alternative, please refer to the EPM6010.

The transducer configuration comes without a display and has a DIN rail mount. It’s ideal for use in switchgear retrofit applications where access to the meter face and display is not necessary, and where budgets are a large consideration.

Features
  • • EPM 6010 Power Meter without display, DIN mount
  • • Mounts directly in ANSI C39.1 (4” round form) or and IEC 92mm DIN square form
  • • Uses minimal panel space with 4.25” panel depth
  • • BACnet/IP Protocol Communications 
  • • 40 BACnet Objects 
  • • Embedded HTTP Server 
  • • 0.2% Watt-Hour Accuracy 

Mounting

EPM6010 Mounting
MULTILIN METER ENCLOSURE

Expanding existing switchgear or installing new metering capability can be challenging due to space limitations, downtime and installation and equipment costs. GE's Multilin Meter Enclosure is a pre-wired configured, economical solution for both retrofit expansions and small scale meter installations that allows the expansion of existing switchgear capability without expensive and time-consuming design.

When ordered as a meter option the enclosure provides a factory pre-wired, installation-ready metering solution that further drives energy cost savings, by enabling the measurement of key energy usage information along multiple metering points for new or existing systems.

Ordering the enclosure is simple when selected as an option during meter configuration, ensuring correct pre-wired meter-compatible delivery.

 
Pre-Wired, Configured and Economical Solution for Retrofit and Small Metering Systems
MULTILIN METER ENCLOSURE

Easy and Rapid Installation

  • Factory pre-wired, installation-ready GE metering solution eliminates wiring and associated errors for rapid installation
  • Extend metering capability with new systems and existing switchgear without system installation downtime

Cost-Effective Retrofit Solution

  • Save up to 200% versus the addition of a new switchgear cabinet
  • Compact footprint makes effective use of existing allocated space
  • Allows new installations or the expansion of existing switchgear capability without expensive, time-consuming designs, eliminating system downtime

Reliable and Compatible

  • Backed by a two-year warranty
  • Simple meter option ordering ensures compatibility with GE EPM 2000/6010/6000/7000 meters
  • Comprehensive factory testing of both meter and enclosure together
  • NEMA1 tested and UL/CUL certified

 

Applications (New and Retrofit installations)

  • Industrial Multi-Tenant Monitoring
  • Commercial/Residential Buildings
  • Healthcare Institutions
  • Government Buildings
  • Manufacturing
  • Educational Campuses
 

 


Assembly


MULTILIN METER Assembly
 

 


Diagram